HIOKI CT6862 / CT6863 AC/DC Current Sensor
CT6862-05 50 A AC/DC, ME15W terminal
CT6863 200 A AC/DC, PL23 terminal
CT6863-05 200 A AC/DC, ME15W terminal
|
|
CT6862 |
CT6863 |
|
Rated current |
50 A AC/DC |
200 A AC/DC |
|
Max. allowable input |
100 A rms (requires derating) |
400 A rms (requires derating) |
|
Frequency characteristics |
Amplitude: DC to 1 MHz Phase: DC to 300 kHz |
Amplitude: DC to 500 kHz Phase: DC to 300 kHz |
|
Amplitude and Phase accuracy |
DC ±0.05 % rdg. ±0.01 % f.s. (Phase: Not defined) 16 Hz ≤ f ≤ 400 Hz ±0.05 % rdg. ±0.01 % f.s. (Phase: ±0.2°) Defined to 1 MHz |
DC ±0.05 % rdg. ±0.01 % f.s. (Phase: Not defined) 16 Hz ≤ f ≤ 400 Hz ±0.05 % rdg. ±0.01 % f.s. (Phase: ±0.2°) Defined to 500 kHz |
|
Output voltage |
2 V /rated current value (voltage output with the Sensor Unit, use with a device having a 1 MΩ input resistance or higher) |
2 V /rated current value (voltage output with the Sensor Unit, use with a device having a 1 MΩ input resistance or higher) |
|
Max. rated voltage to earth |
AC/DC 1000 V (50/60 Hz, CAT III ) |
AC/DC 1000 V (50/60 Hz, CAT III ) |
|
Core diameter |
φ 24 mm (0.94 in) |
φ 24 mm (0.94 in) |
|
Operating temperature, humidity |
-30°C to +85°C (-22°F to 185°F), 80% RH or less (with no condensation) |
-30°C to +85°C (-22°F to 185°F), 80% RH or less (with no condensation) |
|
Power supply |
±11 V to ±15 V DC (Power suppled via the Sensor Unit, which supports 100 to 240 V AC) |
±11 V to ±15 V DC (Power suppled via the Sensor Unit, which supports 100 to 240 V AC) |
|
Power consumption |
5 VA max. (at 50 A/55 Hz, ±12 V power requirement) |
6 VA max. (at 200 A/55 Hz, ±12 V power requirement) |
|
Dimensions and mass |
70 mm (2.76 in)W × 100 mm (3.94 in)H × 53 mm (2.09 in)D, 340 g (12.0 oz), cord length: 3 m (9.84 ft) |
70 mm (2.76 in)W × 100 mm (3.94 in)H × 53 mm (2.09 in)D, 350 g (12.3 oz), cord length: 3 m (9.84 ft) |
|
Accessories |
Instruction manual ×1, Mark bands ×6 |
Instruction manual ×1, Mark bands ×6 |
• Applications in the fields of electric and hybrid electric vehicles
• Wide operating temperature range(-30 ℃ to 85 ℃) fit for automobile applications
• Ideal for evaluation of solar power generation and fuel cells to measure battery charge and discharge and the secondary side of inverters
• For observing waveforms to be used with the oscilloscopes or Memory HiCorders (use with SENSOR UNIT)