HIOKI 3283 Leakage Current Clamp Meter
• Indicate 50/60 Hz leak current components with the filtering function
• Monitor leak current conditions in combination with a Memory HiCorder (monitor output, Model 3283 only)
|
|
3283 |
3283-20 |
|
AC Current range |
10.00 m/ 100.0 m/ 1.000/ 10.00/ 200.0 A, 5 ranges, (40 Hz to 2 kHz, True RMS), Basic accuracy: ±1.0 % rdg. ±5 dgt., Guaranteed accuracy: from 1.00 mA |
10.00 m/ 100.0 m/ 1.000/ 10.00/ 200.0 A, 5 ranges, (40 Hz to 2 kHz, True RMS), Basic accuracy: ±1.0 % rdg. ±5 dgt., Guaranteed accuracy: from 1.00 mA |
|
AC Voltage range |
N/A |
N/A |
|
Frequency range |
30.0 Hz to 1000 Hz, 2 ranges, Basic accuracy: ±0.3 % rdg. ±1 dgt. |
30.0 Hz to 1000 Hz, 2 ranges, Basic accuracy: ±0.3 % rdg. ±1 dgt. |
|
Crest factor |
2.5 or less (1.5 at 200 A range) |
2.5 or less (1.5 at 200 A range) |
|
Filter function |
Cut off frequency at filter ON: 180 Hz (-3dB) |
Cut off frequency at filter ON: 180 Hz (-3dB) |
|
Output |
REC output for current: DC 1 V/f.s. (2 V/f.s. at only 200 A range), response time: less than 200 ms. MON output for current: AC 1 V/f.s. (2 V/f.s. at only 200 A range), 5 Hz to 15 kHz frequency bandwidth (-3 dB) |
N/A |
|
Other functions |
Max./ Min./ Average value record, Data hold, Auto power off |
Max./ Min./ Average value record, Data hold, Auto power off |
|
Display |
LCD, max. 2000 dgt., Display refresh rate: 4 times/s (Fast), 1 time/3s (Slow), 4 times/s (bar graph) |
LCD, max. 2000 dgt., Display refresh rate: 4 times/s (Fast), 1 time/3s (Slow), 4 times/s (bar graph) |
|
Power supply |
6LR61 (Stacked alkaline battery) ×1, or 6F22 (Stacked manganese battery), Continuous use: 40 hours (using 6F22), AC adapter 9445-02/-03 |
6LR61 (Stacked alkaline battery) ×1, or 6F22 (Stacked manganese battery), Continuous use: 40 hours (using 6F22) |
|
Core jaw dia. |
φ 40 mm (1.57 in) |
φ 40 mm (1.57 in) |
|
Dimensions and mass |
62 mm (2.44 in) W × 225 mm (8.86 in) H × 39 mm (1.54 in) D, 400 g (14.1 oz) |
62 mm (2.44 in) W × 225 mm (8.86 in) H × 39 mm (1.54 in) D, 400 g (14.1 oz) |
|
Accessories |
Carrying case 9399 ×1, Hand strap ×1, Stacked manganese battery (6F22) ×1, Instruction manual ×1 |
Carrying case 9399 ×1, Hand strap ×1, Alkaline battery (6LR61) ×1, Instruction manual ×1 |
• Measure leak current using highly sensitive 10μA resolution (at 10.00 mA range)
• Indicate 50/60 Hz leak current components with the filtering function
• Monitor leak current conditions in combination with a Memory HiCorder (monitor output, Model 3283 only)
• 3283-20: EN 61010-2-032:2012 Type A to measure uninsulated
hazardous live conductors such as busbars